Features:
● Three / single-phase models with on-line double convesion technology
● DSP (Digital Signal Processors) technology
● Suitable for all kinds of loads (resistive, inductive and non-linear loads etc)
● High overload capability (up to 150%)
● Bypass dual DSP control design to enhance more reliability
● Redundant & parallelable with advanced parallel current-sharing control technology,Optional N+X redundancy parallel up to 8 units
● Cold start and mains start function
● High charging capability
● Standard configuration with output isolation transformer
● Superior protection (surgers, short-circuit, overvoltages, undervoltages, overcharge, reverse connection protection etc)
● Advanced communications (RS232 and USB ports (standard), SNMP, dry contacts and RS485 (options)
● Other options (parallel kits, input isolation transformer, bypass isolation transformer and harmonic suppressor)
model | TD10K |
Norminal capacity(KW) | 10/8 |
battery voltage | 192VDC/384VDC |
Charge current | 6A~20A(adjustable) |
Input voltage | 380VAC±25% |
Input Frequency | 50/60Hz±10% |
Output voltage | 220VAC±1% |
Output frequency | Synchronized with utility in mains mode,50/60Hz±1% in battery mode |
Waveform | Pure Sine Wave |
Total harmonic distortion | Linear load<3%;non-linear load<5% |
Crest factor | 3:1 |
Protection | Short-circuit,overload,overvoltage,undervoltage,low battery,overtemperature,fan fault |
Inverter overload capability | 125%,10min;150%,1min |
Transfer time | 0ms |
Operating temperature | -20~40℃ |
Relative humidity | 0~90% |
Running high(maximum) | <1000(each additional 100 meters power fell 1% to a maximum 4,000 meters) |
Cooling | Forced ventilation |
Noise | ≤53DB(Distance 1m) |
Size | 360*625*990(192V) & 630*650*1130(384V) (W*H*D mm) |
Contact us for updated pricing and samples